Vol. 99-B, Issue SUPP_22 | Pages 61 - 61
1 Dec 2017
Davies G Bradford N Oliver R Verheul R Bruce W Walsh W
Full Access

Aim

The prevention of surgical-site infection (SSI) is of great importance. Airborne particulate correlates with microbial load and SSI. There are many potential sources of airborne particulates in theatre and from an experimental point of view impossible to control. We evaluated the effectiveness of a novel air decontamination-recirculation system (ADRS) in reducing airborne particles in a laboratory environment and controlled the introduction of particulate using diathermy.

Methods

Airborne particles were measured with and without activation of the ADRS in PC2 laboratory to provide a baseline. Particles were generated in a controlled manner utilising electrocautery ablation of porcine skin tissue. Ablation was performed at 50W power (Cut) for 60 seconds at a constant rate with and without the ADRS operating in the PC2 laboratory. Particles were measured continuously in 30s intervals at two sites 0.5m and 3m from the site of diathermy. Adequate time was allowed for return to baseline between each repetition. Each experiment was repeated 10 times.